Full-Scale Fire Experiment on Mezzanine Racks in Logistics Facilities

The increased demand for contactless services has facilitated a rapid increase in logistics facilities. There are shorter distances between the shelf racks used in mezzansine racks in such facilities compared to standard racks and can store various items; however, research on fire safety related to this remains insufficient. In this study, we visited four logistics facilities with mezzanine racks and one logistics facility using shelf racks to investigate their fundamental characteristics. Considering the characteristics of logistics facilities that store various combustibles, a fire test was conducted using unit shelf racks with packaging materials, boxes, and expandable polystyrene (EPS). Shelf racks loaded with corrugated fiberboard, cardboard boxes, and EPS exhibited the highest fire risk and were set as combustibles inside the rack. Before the experiment, the radiative heat flux was measured by considering the spacing distances of mezzanine racks observed on-site. The most frequently measured range was 43.7–67.3 kW/m2 at 1.0–1.5 m. After beginning the fire experiment, when simulating mezzanine racks with aisle widths of 1.2–2.0 m, fire owing to radiative heat occurred within 5 min in the separated shelf racks. Based on the results, we estimate that the minimum separation distance required to prevent radiant heat-based fires between shelving racks inside a mezzanine is 3.2 m. These findings are expected to be utilized in fire prevention by increasing the understanding of the spread of fire in shelf racks.

Authors

Institutions

Publication Details

Journal
Fire
Published
2024-09-20
DOI
https://doi.org/10.3390/fire7090326
Citations
1
Primary Topic
Fire dynamics and safety research
Type
article
Field-Weighted Citation Impact
0.36

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Full-Scale Fire Experiment on Mezzanine Racks in Logistics Facilities

Lee Byeong-Heun, Jeongki Min, Nam Jeon
1 citations
Fire
Fire dynamics and safety research
0.36
article

Full-Scale Fire Experiment on Mezzanine Racks in Logistics Facilities

Lee Byeong-Heun, Jeongki Min, Nam Jeon
article en
1 citations

Abstract

The increased demand for contactless services has facilitated a rapid increase in logistics facilities. There are shorter distances between the shelf racks used in mezzansine racks in such facilities compared to standard racks and can store various items; however, research on fire safety related to this remains insufficient. In this study, we visited four logistics facilities with mezzanine racks and one logistics facility using shelf racks to investigate their fundamental characteristics. Considering the characteristics of logistics facilities that store various combustibles, a fire test was conducted using unit shelf racks with packaging materials, boxes, and expandable polystyrene (EPS). Shelf racks loaded with corrugated fiberboard, cardboard boxes, and EPS exhibited the highest fire risk and were set as combustibles inside the rack. Before the experiment, the radiative heat flux was measured by considering the spacing distances of mezzanine racks observed on-site. The most frequently measured range was 43.7–67.3 kW/m2 at 1.0–1.5 m. After beginning the fire experiment, when simulating mezzanine racks with aisle widths of 1.2–2.0 m, fire owing to radiative heat occurred within 5 min in the separated shelf racks. Based on the results, we estimate that the minimum separation distance required to prevent radiant heat-based fires between shelving racks inside a mezzanine is 3.2 m. These findings are expected to be utilized in fire prevention by increasing the understanding of the spread of fire in shelf racks.

FireVol. 7(9)
Korea Institute of Civil Engineering and Building Technology (KR), Korea Testing Laboratory (KR)
Ministry of Land, Infrastructure and Transport
Openalex Percentile: Top 40%
Fire dynamics and safety research
0.36
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Full-Scale Fire Experiment on Mezzanine Racks in Logistics Facilities — Lee Byeong-Heun, Jeongki Min, et al. · Fire (2024) | TGRS Research Map | TGRS