This paper analyzed the cause of an insulation breakdown accident in the stator winding of a weather protected(WPII) high-voltage motor(1300kW, 6.6kV) that has been in operation for 27 years. As a result of the insulation diagnosis test conducted 1 year and 6 months before the accident, the polarization index, alternating current, and dielectric loss tangent test results were good, but the partial discharge test result was measured at 13,000pC and was evaluated as a condition requiring attention. In order to analyze the cause of the insulation breakdown of this motor, the damaged winding was cut and analyzed in detail, and no traces of insulation deterioration of the main insulator were found. Contamination was partially confirmed on the surface of the end winding, but it was also difficult to find traces of tracking. As a result of dismantling and analyzing the wires inside the winding, turn shorts were confirmed in two wires. Therefore, even if the high-voltage motor insulation diagnosis test result is judged to be good, it is necessary to comprehensively analyze the possibility of turn short circuit due to insulation deterioration inside of the main insulating material, tracking due to contamination, and deterioration of wire insulation.

Authors

Publication Details

Journal
The Transactions of The Korean Institute of Electrical Engineers
Published
2024-08-31
DOI
https://doi.org/10.5370/kiee.2024.73.8.1461
Citations
1
Primary Topic
Power Line Inspection Robots
Type
article
Field-Weighted Citation Impact
0.21
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Analysis of Insulation Breakdown in Slot End of Stator Windings of High Voltage Motor

Young-Chul Bae, Hoyeol Yoon
1 citations
The Transactions of The Korean Institute of Electrical Engineers
Power Line Inspection Robots
0.21
article

Analysis of Insulation Breakdown in Slot End of Stator Windings of High Voltage Motor

Young-Chul Bae, Hoyeol Yoon
article en
1 citations

Abstract

This paper analyzed the cause of an insulation breakdown accident in the stator winding of a weather protected(WPII) high-voltage motor(1300kW, 6.6kV) that has been in operation for 27 years. As a result of the insulation diagnosis test conducted 1 year and 6 months before the accident, the polarization index, alternating current, and dielectric loss tangent test results were good, but the partial discharge test result was measured at 13,000pC and was evaluated as a condition requiring attention. In order to analyze the cause of the insulation breakdown of this motor, the damaged winding was cut and analyzed in detail, and no traces of insulation deterioration of the main insulator were found. Contamination was partially confirmed on the surface of the end winding, but it was also difficult to find traces of tracking. As a result of dismantling and analyzing the wires inside the winding, turn shorts were confirmed in two wires. Therefore, even if the high-voltage motor insulation diagnosis test result is judged to be good, it is necessary to comprehensively analyze the possibility of turn short circuit due to insulation deterioration inside of the main insulating material, tracking due to contamination, and deterioration of wire insulation.

The Transactions of The Korean Institute of Electrical EngineersVol. 73(8)
Affordable and clean energy
Openalex Percentile: Top 52%
Power Line Inspection Robots
0.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.