Night cooling by hybrid ventilation – analytical predictions of the purge time

Many low-energy buildings rely on a night purge strategy during periods of excessively warm weather in order to flush out excess heat and thereby help prevent overheating on the following day. A typical purge utilises either a mechanical or a natural displacement ventilation strategy. However, we investigate purging by the simultaneous application of natural and mechanical ventilation, i.e. using a hybrid strategy. Hybrid ventilation is widely promoted as a means of overcoming the inherent limitations of both natural and mechanical ventilation, although relatively little is understood about its operation on a fundamental level. Such was the lack of knowledge on hybrid ventilation that even the time taken to complete a purge was not known at the outset of this work. Through the development of a mathematical model, supported by a series of laboratory experiments, we show that the time taken to purge a room using hybrid ventilation can be established analytically, and is controlled by two ratios: (i) the flow rate of the mechanical supply (the ‘forcing’) relative to the initial flow rate through the vents in the absence of mechanical forcing, and (ii) the ratio of the floor-level and ceiling-level vent areas. The analytical predictions show close agreement with our measurements. Supplementing a natural displacement ventilation strategy with even a modest mechanical supply can reduce significantly the time taken to purge warm air from a room. Some of the implications of our findings for preventing overheating in buildings by increasing the efficacy of a night cooling strategy are discussed. Practical Application This research is directly applicable to practitioners involved in the first-order design of hybrid ventilation systems – particularly designs which incorporate a ‘night purge’ regime. Governing equations are derived and the key parameters controlling the rate of purging of warm air are revealed, allowing informed first-order design decisions to be made without the need for expensive and time-consuming computational simulations.

Authors

Institutions

Publication Details

Journal
Building Services Engineering Research and Technology
Published
2024-09-01
DOI
https://doi.org/10.1177/01436244241262605
Citations
4
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
1.06

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Night cooling by hybrid ventilation – analytical predictions of the purge time

Gary R. Hunt, Matthew Waterson
4 citations
Building Services Engineering Research and Technology
Building Energy and Comfort Optimization
1.06
article

Night cooling by hybrid ventilation – analytical predictions of the purge time

Gary R. Hunt, Matthew Waterson
article en
4 citations

Abstract

Many low-energy buildings rely on a night purge strategy during periods of excessively warm weather in order to flush out excess heat and thereby help prevent overheating on the following day. A typical purge utilises either a mechanical or a natural displacement ventilation strategy. However, we investigate purging by the simultaneous application of natural and mechanical ventilation, i.e. using a hybrid strategy. Hybrid ventilation is widely promoted as a means of overcoming the inherent limitations of both natural and mechanical ventilation, although relatively little is understood about its operation on a fundamental level. Such was the lack of knowledge on hybrid ventilation that even the time taken to complete a purge was not known at the outset of this work. Through the development of a mathematical model, supported by a series of laboratory experiments, we show that the time taken to purge a room using hybrid ventilation can be established analytically, and is controlled by two ratios: (i) the flow rate of the mechanical supply (the ‘forcing’) relative to the initial flow rate through the vents in the absence of mechanical forcing, and (ii) the ratio of the floor-level and ceiling-level vent areas. The analytical predictions show close agreement with our measurements. Supplementing a natural displacement ventilation strategy with even a modest mechanical supply can reduce significantly the time taken to purge warm air from a room. Some of the implications of our findings for preventing overheating in buildings by increasing the efficacy of a night cooling strategy are discussed. Practical Application This research is directly applicable to practitioners involved in the first-order design of hybrid ventilation systems – particularly designs which incorporate a ‘night purge’ regime. Governing equations are derived and the key parameters controlling the rate of purging of warm air are revealed, allowing informed first-order design decisions to be made without the need for expensive and time-consuming computational simulations.

Building Services Engineering Research and TechnologyVol. 45(5)
University of Cambridge (GB)
Engineering and Physical Sciences Research Council
Openalex Percentile: Top 25%
Building Energy and Comfort Optimization
1.06
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.