Influence of Induction Machine Loads on Islanding Detection by Inverter-Based Distributed Generation

An inverter-based distributed generation system with an interface unit called power conditioning subsystem (PCS) is required to prevent unintentional islanding immediately. Although the run-on time increases in a local isolated grid that includes an induction machine, the mechanism has not been clarified. In this study, first, an anti-islanding test system used for the PCS certification test in Japan was set up, and it was found that most of the reactive power provided by the PCS to promote frequency deviations was absorbed by the connected induction machine. Second, a modified equivalent circuit of a three-phase induction machine was proposed to simulate their behaviors numerically. The simulation results showed good agreement with the experimental results. Especially, the transient absorption of negative reactive power by the induction machine was accurately reproduced. Third, to investigate the mechanism behind the prolongation of the run-on time, the influence of the inertia of the induction machine was analyzed. It was found that there are worst values of moment of inertia that cause the least frequency fluctuation and the longest run-on time under respective islanding conditions. The results of this study contribute to a better understanding of the behavior and influence of induction machines under an islanding condition.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Power Delivery
Published
2024-09-02
DOI
https://doi.org/10.1109/tpwrd.2024.3452775
Citations
2
Primary Topic
Islanding Detection in Power Systems
Type
article
Field-Weighted Citation Impact
0.42

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Influence of Induction Machine Loads on Islanding Detection by Inverter-Based Distributed Generation

Junji Kondoh
2 citations
IEEE Transactions on Power Delivery
Islanding Detection in Power Systems
0.42
article

Influence of Induction Machine Loads on Islanding Detection by Inverter-Based Distributed Generation

Junji Kondoh
article en
2 citations

Abstract

An inverter-based distributed generation system with an interface unit called power conditioning subsystem (PCS) is required to prevent unintentional islanding immediately. Although the run-on time increases in a local isolated grid that includes an induction machine, the mechanism has not been clarified. In this study, first, an anti-islanding test system used for the PCS certification test in Japan was set up, and it was found that most of the reactive power provided by the PCS to promote frequency deviations was absorbed by the connected induction machine. Second, a modified equivalent circuit of a three-phase induction machine was proposed to simulate their behaviors numerically. The simulation results showed good agreement with the experimental results. Especially, the transient absorption of negative reactive power by the induction machine was accurately reproduced. Third, to investigate the mechanism behind the prolongation of the run-on time, the influence of the inertia of the induction machine was analyzed. It was found that there are worst values of moment of inertia that cause the least frequency fluctuation and the longest run-on time under respective islanding conditions. The results of this study contribute to a better understanding of the behavior and influence of induction machines under an islanding condition.

IEEE Transactions on Power DeliveryVol. 39(5)
Tokyo University of Science (JP)
New Energy and Industrial Technology Development Organization
Affordable and clean energy
Openalex Percentile: Top 38%
Islanding Detection in Power Systems
0.42
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Influence of Induction Machine Loads on Islanding Detection by Inverter-Based Distributed Generation — Junji Kondoh · IEEE Transactions on Power Delivery (2024) | TGRS Research Map | TGRS