An Oscillation Stability Analysis of a Direct-Driven Wind Power Grid-Connected System Considering Low Voltage Ride though from an Energy Perspective

To solve the problem of the oscillation stability of direct-driven wind-powered grid-connected systems with a low-voltage crossing control, a method of oscillation stability analysis for these systems, based on interactive energy, is proposed in this paper. Firstly, a dynamic energy model of a direct-driven wind-powered grid-connected system is established, considering a low-voltage traverse control. Secondly, the energy is divided into four parts—the line parameter energy, current inner loop energy, PLL energy, and current inner loop–PLL interaction energy—and the conduction path of the energy during a low-voltage crossing is described. On this basis, the aperiodic components of each energy path are analyzed, the stability level of the system is quantified, the influence of the different control parameters on the interactive energy dissipation is deduced, the key interactive control links affecting the stability of the system are screened, and the influence rules of the parameters are expounded. Finally, a direct-driven wind-powered grid-connected system model is built on the Rt-lab platform, and it is verified by a simulation test. The results show that the interaction energy generated by the interaction of the current inner loop and phase-locked loop is a key factor affecting the stability of the direct-driven wind-powered grid-connected system. The simulation test parameters of the control group were adjusted as the current inner loop’s proportion parameter increased from 1.32 to 5.28, the current inner loop’s integral parameter increased from 4.48 to 6.42, the PLL’s proportion parameter decreased from 9.45 to 6.3, and the PLL’s integral parameter decreased from 50.25 to 40.2. Both the theoretical and experimental results show that increasing the current inner loop’s integral and proportion parameters can improve the stability level of the direct-driven wind-powered grid-connected system; reducing the phase-locked loop’s proportion and integral parameters can also improve the stability level of the grid-connected system.

Authors

Institutions

Publication Details

Journal
Electronics
Published
2024-09-02
DOI
https://doi.org/10.3390/electronics13173489
Citations
1
Primary Topic
Microgrid Control and Optimization
Type
article
Field-Weighted Citation Impact
0.33
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

An Oscillation Stability Analysis of a Direct-Driven Wind Power Grid-Connected System Considering Low Voltage Ride though from an Energy Perspective

Xiaoming Zou, Yingjie Hu, Chenggen Wang, Bixing Ren et al.
1 citations
Electronics
Microgrid Control and Optimization
0.33
article

An Oscillation Stability Analysis of a Direct-Driven Wind Power Grid-Connected System Considering Low Voltage Ride though from an Energy Perspective

Xiaoming Zou, Yingjie Hu, Chenggen Wang, Bixing Ren, Qiang Li, Dajiang Wang
article en
1 citations

Abstract

To solve the problem of the oscillation stability of direct-driven wind-powered grid-connected systems with a low-voltage crossing control, a method of oscillation stability analysis for these systems, based on interactive energy, is proposed in this paper. Firstly, a dynamic energy model of a direct-driven wind-powered grid-connected system is established, considering a low-voltage traverse control. Secondly, the energy is divided into four parts—the line parameter energy, current inner loop energy, PLL energy, and current inner loop–PLL interaction energy—and the conduction path of the energy during a low-voltage crossing is described. On this basis, the aperiodic components of each energy path are analyzed, the stability level of the system is quantified, the influence of the different control parameters on the interactive energy dissipation is deduced, the key interactive control links affecting the stability of the system are screened, and the influence rules of the parameters are expounded. Finally, a direct-driven wind-powered grid-connected system model is built on the Rt-lab platform, and it is verified by a simulation test. The results show that the interaction energy generated by the interaction of the current inner loop and phase-locked loop is a key factor affecting the stability of the direct-driven wind-powered grid-connected system. The simulation test parameters of the control group were adjusted as the current inner loop’s proportion parameter increased from 1.32 to 5.28, the current inner loop’s integral parameter increased from 4.48 to 6.42, the PLL’s proportion parameter decreased from 9.45 to 6.3, and the PLL’s integral parameter decreased from 50.25 to 40.2. Both the theoretical and experimental results show that increasing the current inner loop’s integral and proportion parameters can improve the stability level of the direct-driven wind-powered grid-connected system; reducing the phase-locked loop’s proportion and integral parameters can also improve the stability level of the grid-connected system.

ElectronicsVol. 13(17)
Shanghai Electric (China) (CN)
Affordable and clean energy
Openalex Percentile: Top 43%
Microgrid Control and Optimization
0.33
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.