Cause analysis of the compression spring stress relaxation of circuit breaker operating mechanism in a 220 kV Substation

Abstract The energy storage compression spring of the LW35-126 circuit breaker operating mechanism has become stress-relaxed in a 220 kV substation after only one year. It was found that the height of the failed spring was 23 mm shorter than that of the new spring of this model during the first annual maintenance. In order to analyze the reason for 60Si2CrVA spring stress relaxation, the stress state of the spring service was analyzed according to the service status. By analyzing the tensile strength, composition, hardness, and microstructure of failed springs, it was found that the main cause of stress relaxation is the incorrect tempering temperature of the 60Si2CrVA spring. Excessive tempering temperature led to coarse massive ferrite and coarsened carbides, reducing the activation energy of the material’s stress process and causing premature stress relaxation failure of the spring material.

Authors

Institutions

Publication Details

Journal
Journal of Physics Conference Series
Published
2024-08-01
DOI
https://doi.org/10.1088/1742-6596/2819/1/012071
Primary Topic
Smart Grid and Power Systems
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Cause analysis of the compression spring stress relaxation of circuit breaker operating mechanism in a 220 kV Substation

Pengfei He, Hanyang Chen, Jun Hu, Liang Qin et al.
Journal of Physics Conference Series
Smart Grid and Power Systems
article

Cause analysis of the compression spring stress relaxation of circuit breaker operating mechanism in a 220 kV Substation

Pengfei He, Hanyang Chen, Jun Hu, Liang Qin, Dingjie Shen, Yi Xie, Qiang Yao, Xiaoxiong Ding
article en

Abstract

Abstract The energy storage compression spring of the LW35-126 circuit breaker operating mechanism has become stress-relaxed in a 220 kV substation after only one year. It was found that the height of the failed spring was 23 mm shorter than that of the new spring of this model during the first annual maintenance. In order to analyze the reason for 60Si2CrVA spring stress relaxation, the stress state of the spring service was analyzed according to the service status. By analyzing the tensile strength, composition, hardness, and microstructure of failed springs, it was found that the main cause of stress relaxation is the incorrect tempering temperature of the 60Si2CrVA spring. Excessive tempering temperature led to coarse massive ferrite and coarsened carbides, reducing the activation energy of the material’s stress process and causing premature stress relaxation failure of the spring material.

Journal of Physics Conference SeriesVol. 2819(1)
Hunan Xiangdian Test Research Institute (China) (CN), Yueyang Changling Equipment Research Institute (China) (CN), Nanjing Boiler and Pressure Vessel Inspection Institute (CN), Xiangtan University (CN)
Affordable and clean energy
Openalex Percentile: Top 90%
Smart Grid and Power Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Cause analysis of the compression spring stress relaxation of circuit breaker operating mechanism in a 220 kV Substation — Pengfei He, Hanyang Chen, et al. · Journal of Physics Conference Series (2024) | TGRS Research Map | TGRS